Veins
| Multi-stranded copper wire class 5 according to EN 60228
|
Insulation
| Cross-linked polyethylene XLPE
|
Insulation colors
| Black, grey, brown, yellow-green
|
center | Parallel stranded conductors
|
Common shield
| aluminised polyester tape with tinned copper braid
|
Coating
| Special halogen-free, self-extinguishing, flame-retardant, orange coloured
|
Operating temperature
|
- Suitable for fixings from -30°C to +70°C
- Suitable for mobile installations from -5°C to +70°C
|
Operating voltage
| 0.6/1 kV
|
Bending radius
|
- Diameters up to 12 mm - Minimum bending radius 5 x cable diameter
- Diameter from 12 mm to 20 mm - min. bending radius 7.5 x cable diameter
- From 20 mm diameter - minimum bend radius 10 x cable diameter
|
Application
| The cable has a special construction for supplying power from the frequency converter to the motor while maintaining full electromagnetic compatibility, it is suitable for both fixed installations and mobile connections, it can be used for industrial equipment, process lines, machines operating in dry and humid rooms, as well as in public places, the cable is made entirely of halogen-free materials, which do not emit toxic substances in case of fire conditions, the cable is not suitable for outdoor installations and direct underground installation |
Technical parameters
|
- Capacitance: Conductor/Inductance = 70 to 250 nF/km
- Conductor/Inductance = 110 to 410 nF/km
- Maximum conductor temperature 70°C
|
Packaging
| discs, reels
|